Device Functions Proline Promass 83 MODBUS RS485 7 Block OUTPUTS
Endress+Hauser 85
Function description
OUTPUTS PULSE/FREQUENCY OUTPUT 1 CONFIGURATION (STATUS)
ASSIGN STATUS
MODBUS register:
Data type:
Access:
4241
3236
Integer
read/write
! Note!
Function is not available unless the STATUS setting was selected in the
OPERATION MODE function (4200).
Use this function to assign a switching function to the status output.
Options:
0 = OFF
1 = ON (operation)
2 = FAULT MESSAGE
3 = NOTICE MESSAGE
4 = FAULT MESSAGE or NOTICE MESSAGE
5 = EMPTY PIPE DETECTION (only with active function)
6 = FLOW DIRECTION
7 = MASS FLOW LIMIT VALUE
8 = VOLUME FLOW LIMIT VALUE
14 = CORRECTED VOLUME FLOW LIMIT VALUE
15 = DENSITY LIMIT VALUE
16 = REFERENCE DENSITY LIMIT VALUE
17 = TEMPERATURE LIMIT VALUE
19 = TOTALIZER 1 LIMIT VALUE
20 = TOTALIZER 2 LIMIT VALUE
21 = TOTALIZER 3 LIMIT VALUE
Advanced selection: with the optional SW package CONCENTRATION
30 = LIMIT TARGET MASS FLOW
31 = LIMIT TARGET % MASS PROPORTION FLOW
32 = LIMIT TARGET VOLUME FLOW
33 = LIMIT TARGET % VOLUME PROPORTION FLOW
34 = LIMIT TARGET CORRECTED VOLUME FLOW
35 = LIMIT CARRIER MASS FLOW
36 = LIMIT CARRIER % MASS PROPORTION FLOW
37 = LIMIT CARRIER VOLUME FLOW
38 = LIMIT CARRIER % VOLUME PROPORTION FLOW
39 = LIMIT CARRIER CORRECTED VOLUME FLOW
40 = LIMIT % BLACK LIQUOR
41 = LIMIT °BAUME > 1
42 = LIMIT °BAUME < 1
43 = LIMIT °API
44 = LIMIT °PLATO
45 = LIMIT °BALLING
46 = LIMIT °BRIX
47 = LIMIT OTHER (_ _ _ _ flexible concentration)
Advanced selection: with the optional SW package ADVANCED DIAGNOSIS
84 = LIMIT MASS FLOW DEVIATION
85 = LIMIT DENSITY DEVIATION
86 = LIMIT REFERENCE DENSITY DEVIATION
87 = LIMIT TEMPERATURE DEVIATION
88 = LIMIT TUBE DAMPING DEVIATION
89 = LIMIT ELECTRODYNAMIC SENSOR DEVIATION
112 = OPERATING FREQUENCY FLUCTUATION DEVIATION
113 = TUBE DAMPING FLUCTUATION DEVIATION
Factory setting: FAULT MESSAGE
! Note!
The behavior of the status output is a normally closed behavior, in other words
the output is closed (transistor conductive) when normal, error-free measuring
is in progress.
– “normal, error-free” operation: Flow direction = forwards; limit values = not
exceeded; no empty or partially filled measuring tube (EPD/OED); no fault or
notice message present.
– Switching response like relay output, see Page 100
If you select OFF, the only function shown in the CONFIGURATION function
group is this function, in other words ASSIGN STATUS (4241).
Switching response like relay output, see Page 100.