3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
134 Endress+Hauser
Main Line
Multiplex -
Assign
AUTO - OOS Use this parameter to define the second reading to be displayed in
the main line alternately (every 10 seconds) with the value defined in
the "User Interface Main Line - Assign" parameter.
Options:
OFF
VOLUME FLOW CH1
VOLUME FLOW CH2
CALC. VOLUME FLOW
VOLUME FLOW % CH1
VOLUME FLOW % CH2
CALC. VOLUME FLOW %
SOUND VELOCITY CH1
SOUND VELOCITY CH2
SOUND VELOCITY AVG.
SIGNAL STRENGTH CH1
SIGNAL STRENGTH CH2
FLOW VELOCITY CH1
FLOW VELOCITY CH2
FLOW VELOCITY AVG.
TOTALIZER 1
TOTALIZER 2
TOTALIZER 3
AI 1 - OUT VALUE
AI 2 - OUT VALUE
AI 3 - OUT VALUE
AI 4 - OUT VALUE
AI 5 - OUT VALUE
AI 6 - OUT VALUE
AI 7 - OUT VALUE
AI 8 - OUT VALUE
PID - IN VALUE (controlled variable)
PID - CAS IN VALUE (remote setpoint value)
PID - OUT VALUE (manipulated variable)
Factory setting:
OFF
Main Line
Multiplex -
100%-Value
AUTO - OOS
Note!
The input is not active unless one of the following was selected in the
"Main - Multiplex Line Assign" parameter:
• VOLUME FLOW % CH1
• VOLUME FLOW % CH2
• CALC. VOLUME FLOW %
Use this parameter to define the flow value to be shown on the
display as the 100% value.
User input:
5-digit floating-point number
Factory setting:
Depends on country, [value] / [dm³...m³ or US-gal...US-Mgal]
Note!
The unit is taken from the “System Unit - Volume Flow” parameter,
(see Page 110).
“TRANSDUCER_DISP” (E+H parameters) / base index 1500
Parameter Write access
with operating
mode
(MODE_BLK)
Description