8 Block SUPERVISION PROline Prosonic Flow 93 FOUNDATION Fieldbus
72 Endress+Hauser
VALUE SIMULATION
MEASURAND
(8044)
Note!
This function is not displayed unless the SIMULATION
MEASURAND (8043) function is active.
Use this function to specify a selectable value, (e.g. 12 m³/s). This is used to
test the associated functions in the flowmeter itself and downstream
FOUNDATION Fieldbus function blocks.
User input:
5-digit floating-point number, [unit]
Factory setting:
0 [unit]
Caution!
• The setting is not saved if the power supply fails.
• The appropriate unit is taken from the SYSTEM UNITS function group, (ACA,
see Page 15).
SYSTEM RESET
(8046)
Use this function to perform a reset of the measuring system.
Options:
NO
RESTART SYSTEM (restart without interrupting power supply)
Factory setting:
NO
TROUBLESHOOTING
(8047)
Use this function to rectify errors in the EEPROM. The EEPROM is divided into
a number of blocks. Only blocks in which a fault has occurred are shown. For
fault elimination, select the block in question and acknowledge by pressing the
key.
Caution!
When you clear an error in a block, the parameters of the block you select are
reset to their factory settings.
Options:
CANCEL
”Faulty block”
Function description
SUPERVISION → SYSTEM → OPERATION