7 Block BASIC FUNCTION PROline Prosonic Flow 93 FOUNDATION Fieldbus
50 Endress+Hauser
7.1 Group FOUNDATION FIELDBUS
7.1.1 Function group: CONFIGURATION
BASIC FUNCTION G Þ FOUNDATION FIELDBUS GGA Þ CONFIGURATION 620
Function description
BASIC FUNCTION → FOUNDATION FIELDBUS → CONFIGURATION
WRITE PROTECT
(6200)
Use this function to check whether the device parameters can be accessed
via the FOUNDATION Fieldbus.
Display:
OFF
Access to device parameters via FOUNDATION Fieldbus possible
ON
Access to device parameters via FOUNDATION Fieldbus not possible
Factory setting:
OFF
Note!
Hardware write protection is enabled and disabled by means of a jumper on
the I/O board, (see also Operating Instructions for Prosonic Flow 93
FOUNDATION Fieldbus BA078D/06/en/).
SIMULATION
(6201)
Use this function to check whether a simulation in the Analog Input or
Discrete Output function block is possible.
Display:
OFF
Simulation in the Analog Input and Discrete Output function block is not
possible.
ON
Simulation in the Analog Input and Discrete Output function block is
possible.
Factory setting:
ON
Note!
• The simulation mode is activated and deactivated by means of a jumper
on the I/O board, (see also Operating Instructions for Prosonic Flow 93
FOUNDATION Fieldbus BA078D/06/en/).
• The status of the simulation mode is also shown in the “BLOCK_ERR”
parameter of the Resource Block, (see Page 92).
DEVICE PD-TAG
(6203)
Use this function to enter a tag name for the measuring device.
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,-, punctuation marks
Factory setting:
E+H_PROSONIC_FLOW_93_XXXXXXXXXXX
(XXXXXXXXXXX = serial number)