PROline Prosonic Flow 93 FOUNDATION Fieldbus 7 Block BASIC FUNCTION
Endress+Hauser 59
WALL THICKNESS
(6527)
Use this function to enter the thickness of the pipe walls.
Measuring the wall thickness
If the wall thickness is not known, it can be measured.
To do so, WALL THICKNESS must be set in the MEASUREMENT function
(6880, Page 63). The wall thickness is measured by calling up the WALL
THICKNESS (6527) function. The measured wall thickness, the signal strength
and a bar graph appear on the local display.
The measurement is valid if 100% is achieved in the bar graph.
If you confirm the function with the
key, the SAVE prompt appears. To accept
the measured wall thickness, select the option YES by means of the
or
key.
User input:
Fixed-point number 0.1...100.0 mm
Factory setting:
3.2 mm
LINER MATERIAL
(6528)
Use this function to select the liner material of the pipe.
Options:
NO LINER
MORTAR
RUBBER
TAR EPOXY
OTHERS
Factory setting:
NO LINER
SOUND VELOCITY
LINER
(6529)
Note!
This function does not appear unless a liner was selected in the LINER
MATERIAL (6528) function.
Use this function to enter the sound velocity of the liner.
User input:
Fixed-point number 800...6500 m/s
Factory setting:
Depends on the setting selected in the LINER MATERIAL (6528) function
LINER THICKNESS
(6530)
Note!
This function does not appear unless a liner was selected in the LINER
MATERIAL (6528) function.
Use this function to enter the thickness of the liner.
User input:
Fixed-point number 0.1...100.0 mm
Factory setting:
0 mm
Function description
BASIC FUNCTION PROCESS PARAMETER (CH1...CH2) PIPE DATA