8 Block SUPERVISION PROline Prosonic Flow 93 FOUNDATION Fieldbus
70 Endress+Hauser
8.1 Group SYSTEM
8.1.1 Function group: CONFIGURATION
SUPERVISION J
Þ
SYSTEM JAA
Þ
CONFIGURATION 800
Function description
SUPERVISION → SYSTEM → CONFIGURATION
ALARM DELAY
(8005)
Use this function to specify a time period for suppressing the appearance of
fault or notice messages.
Depending on the setting and the type of fault, this suppression acts on:
• Display
• Output values (AI Blocks) FF interface
User input:
0...100 s (in steps of one second)
Factory setting:
0 s
Caution!
If this function is activated, error and notice messages are delayed by the time
corresponding to the setting before being forwarded to the higher-level
controller (process controller, etc.). It is therefore imperative to check in
advance whether a delay of this nature could affect the safety requirements of
the process. If fault and notice messages may not be suppressed, a value of
0 seconds must be entered here.