Endress+Hauser Proline Prosonic Flow 93 - 8 Block SUPERVISION; Group SYSTEM; Function Group: CONFIGURATION

Endress+Hauser Proline Prosonic Flow 93
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Block SUPERVISION PROline Prosonic Flow 93 FOUNDATION Fieldbus
70 Endress+Hauser
8.1 Group SYSTEM
8.1.1 Function group: CONFIGURATION
SUPERVISION J
Þ
SYSTEM JAA
Þ
CONFIGURATION 800
Function description
SUPERVISION SYSTEM CONFIGURATION
ALARM DELAY
(8005)
Use this function to specify a time period for suppressing the appearance of
fault or notice messages.
Depending on the setting and the type of fault, this suppression acts on:
Display
Output values (AI Blocks) FF interface
User input:
0...100 s (in steps of one second)
Factory setting:
0 s
Caution!
If this function is activated, error and notice messages are delayed by the time
corresponding to the setting before being forwarded to the higher-level
controller (process controller, etc.). It is therefore imperative to check in
advance whether a delay of this nature could affect the safety requirements of
the process. If fault and notice messages may not be suppressed, a value of
0 seconds must be entered here.