PROline Prosonic Flow 93 FOUNDATION Fieldbus 7 Block BASIC FUNCTION
Endress+Hauser 67
7.4.2 Function group: CALIBRATION DATA
BASIC FUNCTION G
Þ
FOUNDATION FIELDBUS GGA
ß
PROCESS PARAM. CH1 GIA
ß
PROCESS PARAM. CH2 GIB
ß
SYSTEM PARAM. CH1 GLA
ß
SYSTEM PARAM. CH2 GLB
ß
SENSOR DATA CH1 GNA
Þ
SENSOR PARAM. 688
ß
CALIBRATION DATA 689
ß
SENSOR DATA CH2 GNB
Þ
SENSOR PARAM. 688
ß
CALIBRATION DATA 689
Function description
BASIC FUNCTION → SENSOR DATA (CH1...CH2) → CALIBRATION DATA
CALIBRATION FACTOR
(6890)
Displays the current calibration factor for the sensors.
ZERO POINT
(6891)
Use this function to call up or manually change the zero point correction
currently being used.
User input:
5-digit floating-point number, including unit and sign (e.g. +10.0 ns)
CORRECTION FACTOR
(6893)
Use this function to enter a correction factor at the client's site.
User input:
5-digit floating-point number
Factory setting:
1.0000 (= no correction)
DEVIATION
SENSOR DISTANCE
(6894)
Note!
This function is not available unless “INSERTION” is selected in the
MEASUREMENT function (6880, see Page 63).
Use this function to enter a deviation value for the sensor distance.
User input:
5-digit floating-point number, including unit and sign (e.g. +2.0000 mm)
Factory setting:
0 mm