EasyManuals Logo

Endress+Hauser Proline Prosonic Flow 93 Function Manual

Endress+Hauser Proline Prosonic Flow 93
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
PROline Prosonic Flow 93 FOUNDATION Fieldbus 5 Block USER INTERFACE
Endress+Hauser 25
X-LINE CALCULATED
MAIN VALUES
(2004)
Use this function to indicate which calculated main value from the measured
values of both channels is displayed.
CALCULATED VOLUME FLOW must be selected in the ASSIGN line
function, (function 2200 for the main line, function 2400 for the additional line,
function 2600 for the information line), so that the value appears in the line
required.
Note!
This function does not appear if OFF was selected on at least one channel in
the MEASUREMENT (6880) function.
Options:
(CH1 + CH2) / 2
CH1 + CH2
CH1 - CH2
Factory setting:
(CH1 + CH2) / 2
Function description
USER INTERFACE CONTROL BASIC CONFIGURATION

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow 93

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Proline Prosonic Flow 93 and is the answer not in the manual?

Endress+Hauser Proline Prosonic Flow 93 Specifications

General IconGeneral
BrandEndress+Hauser
ModelProline Prosonic Flow 93
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals