PROline Prosonic Flow 93 FOUNDATION Fieldbus 5 Block USER INTERFACE
Endress+Hauser 25
X-LINE CALCULATED
MAIN VALUES
(2004)
Use this function to indicate which calculated main value from the measured
values of both channels is displayed.
CALCULATED VOLUME FLOW must be selected in the ASSIGN line
function, (function 2200 for the main line, function 2400 for the additional line,
function 2600 for the information line), so that the value appears in the line
required.
Note!
This function does not appear if OFF was selected on at least one channel in
the MEASUREMENT (6880) function.
Options:
(CH1 + CH2) / 2
CH1 + CH2
CH1 - CH2
Factory setting:
(CH1 + CH2) / 2
Function description
USER INTERFACE CONTROL BASIC CONFIGURATION