2 Resource Block PROline Prosonic Flow 93 FOUNDATION Fieldbus
92 Endress+Hauser
BLOCK_ERR read only Displays the active block error.
Display:
SIMULATION ACTIVE
Simulation possible in the Analog Input function block via the
SIMULATE parameter and in the Discrete Output function block via
the SIMULATE_D parameter, (see also settings for simulation mode
in the Operating Instructions for PROline Prosonic Flow 93
FOUNDATION Fieldbus, BA078D/06/en, Section 5.4).
OUT OF SERVICE
The block has the status "Out of Service".
CLR_FSTATE AUTO - OOS This parameter can be used to manually disable the security
behaviour of the Discrete Output function block.
Options:
UNINITIALIZED
OFF
CLEAR (security behaviour disabled)
Note!
The security behaviour of the Discrete Output function block can be
manually enabled via the SET_FSTATE parameter, (see Page 96).
CONFIRM_
TIME
AUTO - OOS Specifies the confirmation time for the event report. The event
report is sent to the fieldbus host system again if the device does
not receive confirmation within this time.
Factory setting:
640000
1
/
32
ms
CYCLE_SEL AUTO - OOS For selecting and displaying the block execution method used by
the fieldbus host system.
Note!
The block execution method is selected by the fieldbus host
system.
CYCLE_TYPE read only Displays the block execution methods supported by the device.
Display:
SCHEDULED (timed block execution method)
BLOCK EXECUTION (sequential block execution method)
DD_
RESOURCE
read only Displays the reference source for the device description (DD).
Display:
No display
Note!
If there is no DD in the device then nothing is displayed.
Resource Block / base index 258
Parameter Write access with
operating mode
(MODE_BLK)
Description