2 Resource Block PROline Prosonic Flow 93 FOUNDATION Fieldbus
96 Endress+Hauser
RESTART AUTO - OOS This parameter is used to reset the field device in various ways.
Options:
UNINITIALIZED
RUN
Normal operating status.
RESOURCE
(is not supported)
DEFAULTS
The FF standard parameters and the connections of the function
blocks are reset to the specified default values.
PROCESSOR
Warm start of device, processor restart.
RS_STATE read only Displays the current operating status of the Resource Block.
Display:
STANDBY
The Resource Block is in the OOS operating mode. Execution of
the remaining blocks is not possible.
ONLINE LINKING
The connections configured between the function blocks have not
yet been linked.
ONLINE
Normal operating status, the Resource Block is in the AUTO
operating mode. The configured connections between the function
blocks have been made.
SET_FSTATE AUTO - OOS This parameter can be used to manually enable the security
behaviour of the Discrete Output function block.
Options:
UNINITIALIZED
OFF
SET (security behaviour enabled)
Note!
The security behaviour of the Discrete Output function block can be
manually disabled via the CLR_FSTATE parameter, (see Page 92).
SHED_RCAS AUTO - OOS Specifies the monitoring time for checking the connection between
the fieldbus host system and the PID function block in the RCAS
operating mode.
On expiry of the monitoring time, the PID function block switches
from the RCAS operating mode to the operating mode selected in
the SHED_OPT parameter, (see Page 214).
Factory setting:
640000
1
/
32
ms
Resource Block / base index 258
Parameter Write access with
operating mode
(MODE_BLK)
Description

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow 93

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Proline Prosonic Flow 93 and is the answer not in the manual?

Endress+Hauser Proline Prosonic Flow 93 Specifications

General IconGeneral
BrandEndress+Hauser
ModelProline Prosonic Flow 93
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals