PROline Prosonic Flow 93 FOUNDATION Fieldbus 2 Resource Block
Endress+Hauser 97
SHED_ROUT AUTO - OOS Specifies the monitoring time for checking the connection between
the fieldbus host system and the PID function block in the ROUT
operating mode.
On expiry of the monitoring time, the PID function block switches
from the ROUT operating mode to the operating mode selected in
the SHED_OPT parameter, (see Page 214).
Factory setting:
640000
1
/
32
ms
STRATEGY AUTO - OOS Parameter for grouping and thus faster evaluation of blocks.
Grouping is carried out by entering the same numerical value in the
STRATEGY parameter of each individual block.
Factory setting:
0
Note!
These data are neither checked nor processed by the Resource
Block.
ST_REV read only Displays the revision status of the static data.
Note!
The revision status is incremented on each modification of static
data.
TAG_DESC AUTO - OOS Entry of a user-specific text of max. 32 characters for unique
identification and assignment of the block.
Factory setting:
"_ _ _ _ _ _ _ _" no text
TEST_RW AUTO - OOS
Note!
This parameter is required only for the FF-conformance test and is
not significant in normal operation.
UPDATE_EVT read only Displays whether static block data have been modified, including
date and time.
WRITE_ALM AUTO - OOS Displays the status of the write protection alarm.
Note!
• The alarm is triggered if the write protection is disabled.
• If the option of the alarm has not been enabled in the
ACK_OPTION parameter, the alarm can only be acknowledged
via this parameter.
Resource Block / base index 258
Parameter Write access with
operating mode
(MODE_BLK)
Description