PROline Prosonic Flow 93 FOUNDATION Fieldbus 2 Resource Block
Endress+Hauser 95
MANUFAC_ID read only Displays the manufacturer's ID number.
Display:
452B48 (hex) for Endress+Hauser
MAX_NOTIFY read only Displays the maximum number of event reports supported by the
device that can exist unconfirmed at the same time.
Display:
24
MEMORY_
SIZE
read only Displays the available configuration memory in Kbytes.
Note!
This parameter is not supported.
MIN_
CYCLE_T
read only Displays the shortest block execution time which is supported by
PROline Prosonic Flow 93 FOUNDATION Fieldbus.
Display:
1600
1
/
32
ms (≅ 50 ms)
MODE_BLK AUTO - OOS Displays the current (Actual) and desired (Target) operating mode
of the Resource Block, the permitted modes (Permitted) supported
by the Resource Block and the normal operating mode (Normal).
Display:
AUTO (automatic mode)
In this operating mode, the execution of the remaining blocks
(Transducer Blocks, AI, DO and PID function blocks) is enabled.
OOS, Out of Service
The block has the status "Out of Service". In this operating mode,
the execution of the remaining blocks (Transducer Blocks, AI, DO
and PID function blocks) is blocked. These blocks cannot be set to
AUTO mode.
Note!
The current operating status of the Resource Block is also shown
via the RS_STATE parameter, (see Page 96).
NV_CYCLE_T read only Displays the time interval for which the dynamic device parameters
are stored in the non-volatile memory.
The time interval displayed relates to storage of the following
dynamic device parameters:
• OUT
• PV
• FIELD_VAL
Note!
Since PROline Prosonic Flow 93 FF does not store the dynamic
device parameter in the non-volatile memory, this parameter always
displays the value 0
1
/
32
ms.
Resource Block / base index 258
Parameter Write access with
operating mode
(MODE_BLK)
Description