2 Resource Block PROline Prosonic Flow 93 FOUNDATION Fieldbus
94 Endress+Hauser
FEATURES_
SEL
AUTO - OOS For selecting the additional options of the device.
Options:
UNICODE (is not supported)
REPORTS
Event report is sent. The fieldbus host system must acknowledge
receipt of the event report.
FAULTSTATE (is not supported)
The security behaviour of the Discrete Output function block is
supported, (see CLR_FSTATE and SET_FSTATE parameters).
SOFT W LOCK (is not supported)
HARD W LOCK
HW write protection, this option has no effect.
OUT READ BACK (is not supported)
DIRECT WRITE (is not supported)
FREE_TIME read only Displays the free system time (in percent) available for execution of
further function blocks.
Note!
Since the function blocks of PROline Prosonic Flow 93 FF are
permanently configured, this parameter always displays the value
0%.
FREE_SPACE read only Displays the free system memory (in percent) available for
execution of further function blocks.
Note!
Since the function blocks of PROline Prosonic Flow 93 FF are
permanently configured, this parameter always displays the value
0%.
GRANT_
DENY
AUTO - OOS Releases or restricts the access authorisation of a fieldbus host
system to the field device.
Note!
This parameter is not evaluated.
HARD_TYPES read only Displays the input signal type for the function blocks, (Analog Input
and Discrete Output function blocks).
Display:
SCALAR INPUT (scalable analog input value)
DISCRETE OUTPUT
ITK_VER read only Displays the revision state of the Interoperability Test Kits (ITK).
Display:
4
LIM_NOTIFY AUTO - OOS This parameter is used to specify the number of event reports that
can exist unconfirmed at the same time.
Options:
0...24
Factory setting:
24
Resource Block / base index 258
Parameter Write access with
operating mode
(MODE_BLK)
Description