PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 137
Add. Line -
100%-Value
AUTO - OOS
Note!
The input is not active unless one of the following was selected in the
"Add. Line - Assign" parameter:
• VOLUME FLOW % CH1
• VOLUME FLOW % CH2
• CALC. VOLUME FLOW %
• VOLUME FLOW BARGRAPH % CH1
• VOLUME FLOW BARGRAPH % CH2
• CALC. VOLUME FLOW BARGRAPH %
Use this parameter to define the flow value to be shown on the
display as the 100% value.
User input:
5-digit floating-point number
Factory setting:
Depends on country, [value] / [dm³...m³ or US-gal...US-Mgal]
Note!
The unit is taken from the “System Unit - Volume Flow” parameter,
(see Page 110).
Add. Line -
Format
AUTO - OOS
Note!
Selection is not active unless a numerical option was selected in the
"Add. Line - Assign" parameter.
Use this parameter to define the maximum number of places after
the decimal point displayed for the reading in the additional line.
Options:
XXXXX. – XXXX.X – XXX.XX – XX.XXX – X.XXXX
Factory setting:
X.XXXX
Note!
• Note that this setting only affects the reading as it appears on the
display, it has no influence on the accuracy of the system's
calculations.
• The places after the decimal point as computed by the measuring
device cannot always be displayed, depending on this setting
and the engineering unit. In these instances an arrow appears on
the display between the measured value and the engineering unit,
(e.g. 1.2
→ dm³/s), indicating that the measuring system is
computing with more decimal places than can be shown on the
display.
“TRANSDUCER_DISP” (E+H parameters) / base index 1500
Parameter Write access
with operating
mode
(MODE_BLK)
Description