PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 155
Totalizer
Handling -
Reset All
AUTO - OOS Resets totalizers 1–3 (“Totalizer x - System Value” parameter) to
zero simultaneously.
Options:
NO
YES
Factory setting:
NO
Note!
Resetting of the totalizers can be also be controlled or initiated
using cyclic data transmission via the Discrete Output function
block, (see Page 181).
Totalizers
Handling -
Failsafe All
AUTO - OOS Use this parameter to define the common response of all totalizers
(1...3) to error.
Options:
STOP
The totalizer is paused until the fault is rectified.
ACTUAL VALUE
The totalizers continue to count based on the current measured
flow value. The fault is ignored.
HOLD VALUE
The totalizer continues to count the flow is based on the last valid
flow value (before the fault occurred).
Factory setting:
STOP
Amp. Device
Family
read only This parameter is only used in the event of servicing.
“TRANSDUCER_TOT” (E+H parameters) / base index 1550
Parameter Write access
with operating
mode
(MODE_BLK)
Description