PROline Prosonic Flow 93 FOUNDATION Fieldbus 4 Analog Input function block
Endress+Hauser 173
HI_LIM AUTO - MAN -
OOS
Entry of the alarm limit value for the upper warning (HI_ALM). If the
output value OUT exceeds this limit value then the alarm status
parameter HI_ALM is output.
User input:
Range and unit of OUT_SCALE
Factory setting:
3402823466 x 10
38
HI_PRI AUTO - MAN -
OOS
Specifies the action taken when the upper warning limit value
(HI_LIM) is exceeded.
User input:
0
The violation of the upper warning limit is not evaluated.
1
No notification if the upper warning limit is violated.
2
Reserved for block alarms.
3-7
The violation of the upper warning limit is output as a user notice
with the appropriate priority (3 = low priority, 7 = high priority).
8-15
The violation of the upper warning limit is output as a critical alarm
with the appropriate priority (8 = low priority, 15 = high priority).
Factory setting:
0
IO_OPTS OOS Activates the options for processing the input and output values of
the function block (I/O options).
The following options are supported:
Options:
Low Cutoff
Factory setting:
Not enabled
Note!
The switch-on point of the low flow cut off can be entered via the
"LOW_CUT" parameter, (see Page 177).
Analog Input function block /
Base index: AI 1 = 350, AI 2 = 390, AI 3 = 430, AI 4 = 470, AI 5 = 510, AI 6 = 550, AI 7 = 590, AI 8 = 630
Parameter Write access
with operating
mode
(MODE_BLK)