4 Analog Input function block PROline Prosonic Flow 93 FOUNDATION Fieldbus
176 Endress+Hauser
LO_LO_PRI AUTO - MAN -
OOS
Specifies the action taken when the lower alarm limit value
(LO_LO_LIM) is undershot.
User input:
0
The violation of the lower alarm limit is not evaluated.
1
No notification to master if the lower alarm limit is violated.
2
Reserved for block alarms.
3-7
The violation of the lower alarm limit is output as a user notice with
the appropriate priority (3 = low priority, 7 = high priority).
8-15
The violation of the lower alarm limit is output as a critical alarm with
the appropriate priority (8 = low priority, 15 = high priority).
Factory setting:
0
LO_PRI AUTO - MAN -
OOS
Specifies the action taken when the lower warning limit value
(LO_LIM) is exceeded.
User input:
0
The violation of the lower warning limit is not evaluated.
1
No notification to master if the lower warning limit is violated.
2
Reserved for block alarms.
3-7
The violation of the lower warning limit is output as a user notice
with the appropriate priority (3 = low priority, 7 = high priority).
8-15
The violation of the lower warning limit is output as a critical alarm
with the appropriate priority (8 = low priority, 15 = high priority).
Factory setting:
0
Analog Input function block /
Base index: AI 1 = 350, AI 2 = 390, AI 3 = 430, AI 4 = 470, AI 5 = 510, AI 6 = 550, AI 7 = 590, AI 8 = 630
Parameter Write access
with operating
mode
(MODE_BLK)
Description