6 PID function block (PID controller) PROline Prosonic Flow 93 FOUNDATION Fieldbus
196 Endress+Hauser
6.9 Example of configuration
The measuring range of the flowmeter (controlled variable) is 0...30 m
3
/h.
The desired flow value (setpoint value) is specified manually by means of the SP
parameter and should be 15 m
3
/h. The Analog Output function block is actuated over
an output range of 0 ... 100%.
Configuration:
Setting the input range and input unit of the controlled variable at input IN
:
Setting the output range and output unit of the manipulated variable at output OUT:
Defining the input limits for the setpoint value range:
Defining the output limits for the manipulated variable at output OUT:
Setting the bypass function:
In order to be able to deactivate the bypass function via the BYPASS parameter, the
Bypass Enable option must first be activated via the CONTROL_OPTS parameter.
Setting the control parameter (depending on the controlled system):
GAIN - proportional gain factor (P-term)
RESET- time constant for the integral function (I-term)
RATE- time constant for the derivative action (D-term)
Specifying the setpoint value via SP parameter:
SP = 15
Configuration of the limit value and control deviation alarms and associated priorities,
if required.
In order for the PID function block to be executed the operating mode must be set to
AUTO.
PV_SCALE 0 % = 0
PV_SCALE 100% = 30
PV_SCALE UNIT = m
3
/h
OUT_SCALE 0 % = 0
OUT_SCALE 100 % = 100
OUT_SCALE UNIT = %
SP_LO_LIM = 0
SP_HI_LIM = 30
OUT_LO_LIM = 0
OUT_HI_LIM = 100