PROline Prosonic Flow 93 FOUNDATION Fieldbus 6 PID function block (PID controller)
Endress+Hauser 199
ALARM_SUM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Displays the current status of the process alarms.
Display:
HI_HI_ALM
Violation of the upper limit value alarm
HI_ALM
Violation of the upper limit value warning
LO_LO_ALM
Violation of the lower limit value alarm
LO_ALM
Violation of the lower limit value warning
DV_HI_ALM
Violation of the limit value alarm for the upper control deviation
DV_LO_ALM
Violation of the limit value alarm for the lower control deviation
BLOCK_ALM
Block alarm
Note!
In addition, the process alarms can also be disabled in this
parameter group.
ALERT_KEY ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the identification number of the plant unit. This
information can be used by the fieldbus host system for sorting
alarms and events.
User input:
1...255
Factory setting:
0
BAL_TIME ROUT - RCAS -
CAS - AUTO -
MAN - OOS
This parameter is used to enter the time for which the weighting
factor counteracts the integral term of the saturation, (calculated
manipulated variable > OUT_HI_LIM).
Factory setting:
0 s
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description