PROline Prosonic Flow 93 FOUNDATION Fieldbus 6 PID function block (PID controller)
Endress+Hauser 215
SP_HI_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the upper limit of the setpoint value (reference value).
User input:
Range and unit of PV_SCALE ±10%
Factory setting:
100
Note!
If the setting for the end of the scale is changed in the PV_SCALE
parameter this value should be modified accordingly.
SP_LO_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the lower limit of the setpoint value (reference value).
User input:
Value and range of PV_SCALE ±10%
Factory setting:
100
Note!
If the setting for the end of the scale is changed in the PV_SCALE
parameter this value should be modified accordingly.
SP_RATE_DN ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the ramping rate of a diminishing setpoint value in the
AUTO operating mode.
Factory setting:
3402823466 x 10
38
PV per second
Note!
• If the value "0" is entered then this parameter is deactivated
and the setpoint value is used directly.
• The speed restriction is only active in the AUTO operating
mode.
SP_RATE_UP ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the ramping rate of an increasing setpoint value in the
AUTO operating mode.
Factory setting:
3402823466 x 10
38
PV per second
Note!
• If the value "0" is entered then this parameter is deactivated
and the setpoint value is used directly.
• The speed restriction is only active in the AUTO operating
mode.
ST_REV read only Displays the revision status of the static data.
Note!
The revision status parameter is incremented on each
modification of static data.
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description