5. Parameter
5−60
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Jog mode acceleration
PNU PNU: 532 Index: 1 Max index: 1 Class: Var Data type: int32
Values Unit: Acceleration (index = 7)
Linear drive Semi−rotary drive
Dimension Default Minimum Maximum Dimension Default Minimum Maximum
SI 0,001 m/s
2
100 10 100.000 1 °/s
2
100 10 100.000
Imperial 0.01 ft/s
2
30 3 32.808 1 °/s
2
100 10 100.000
Jogging acceleration.
Depending on PNU 521:01, the corresponding default value is used instead, if necessary.
o The parameter value cannot be changed.
o Writing permissible only in commissioning/parametrising mode with disabled controller.
o This parameter can be written by FCT without higher−order controller.
o After writing, controller recalculation is carried out.
Jog mode deceleration
PNU PNU: 533 Index: 1 Max index: 1 Class: Var Data type: int32
Values Unit: Acceleration (index = 7)
Linear drive Semi−rotary drive
Dimension Default Minimum Maximum Dimension Default Minimum Maximum
SI 0,001 m/s
2
500 10 100.000 1 °/s
2
500 10 100.000
Imperial 0.01 ft/s
2
150 3 32.808 1 °/s
2
500 10 100.000
Jogging deceleration.
Depending on PNU 521:01, the corresponding default value is used instead, if necessary.
o The parameter value cannot be changed.
o Writing permissible only in commissioning/parametrising mode with disabled controller.
o This parameter can be written by FCT without higher−order controller.
o After writing, controller recalculation is carried out.