17 Advanced functions
FLUXUS F60* 17.11 Activation of a binary output as alarm output
169
UMFLUXUS_F60xV5-0EN, 2017-10-16
17.11.3 Defining the hysteresis
A hysteresis can be defined for the alarm output R1. This prevents a constant triggering
of the alarm when measured values fluctuate marginally around the limit.
The hysteresis is a symmetrical range around the limit. The alarm will be activated if the
measured values exceed the upper limit and deactivated if the measured values fall be-
low the lower limit.
If the switching condition MIN or MAX is selected in the scroll list func:
Enter a value for the hysteresis or enter zero to work without hysteresis.
Press ENTER.
Example
physical quantity: mass flow rate in kg/h
Quantity Limit: 1kg
Example
physical quantity: mass flow rate in kg/h
Low Limit: 60 kg/h
The unit of measurement of the physical quantity is changed to kg/min. The new limit
to be entered is 1 kg/min.
Example
High Limit: 30 kg/h
Hysterese: 1 kg/h
The alarm is triggered for measured values > 30.5 kg/h and deactivated for measured
values < 29.5 kg/h.
R1 Input:\...\Hysterese

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flexim FLUXUS F60 Series and is the answer not in the manual?

Flexim FLUXUS F60 Series Specifications

General IconGeneral
BrandFlexim
ModelFLUXUS F60 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals