Limitorque QX Electronic Actuator FCD LMENIM3314-01 – 06/18
flowserve.com
6.6.2 Optional Transformer Remounting
Step 1
Position optional transformer assembly (#1) to the 4 M3 taps on the back of the control module chassis plate, see
Figure 6.16 for orientation. Fit the four M3 screws (#2) thru bracket holes aligning with the taps in on the control
module and using a M2.5 hex key tighten the four M3 screws.
Step 2
Connect wiring (See section 7 for wiring connections). Note that the optional transformer wiring harness (#3) must
have the correct wire to connector position per voltage supply (See Table 7.1).

Table of Contents