5.2 Function Code Tables
5-18
Table 5.2-12
r codes: Motor 4 Parameters
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
r
01 Maximum Output Frequency 4 25.0 to 500.0 Hz N Y 60.0 Y Y Y Y Y
r
02 Base Frequency 4 25.0 to 500.0 Hz N Y 50.0 Y Y Y Y Y
r
03 Rated Voltage at Base Frequency 4 0: AVR disabled (Output a voltage in proportion to input
voltage)
80 to 240 V: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500 V: Output an AVR-controlled voltage
(for 400 V class series)
N Y2 200
400
Y Y Y Y Y
*6 The motor parameters are automatically set, depending upon the inverter's capacity. See Table 5.2-18.
*9 These function codes are reserved for particular manufacturers. Do not access these function codes.