Chapter 5. Communication
96 AT600 User’s Manual
Command 152 (0x98): Write Unit Group (cont.)
Table 34: Response Data Bytes for Write Unit Group
Byte Format Description
0 Unsigned-8 Group index:
1: Velocity unit;
2: Actual Volumetric unit;
3: Standard Volumetric unit;
4: Mass unit;
5: Totalizer unit;
6: Density unit;
7: Pipe Dimension;
8: Thermal;
9: Acceleration;
1 Enum unit code
Table 35: Command-Specific Response Codes
for Write Unit Group
Code Class Description
0 Success No Command-Specific Errors
1 Undefined
2 Error Invalid Selection
3 - 4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7Error In Write Protect Mode
8 - 15 Undefined
16 Error Access Restricted
17 - 127 Undefined