Chapter 5. Communication
104 AT600 User’s Manual
Command 172 (0xAC): Set Analog Measurement Range Values (cont.)
Command 173 (0xAD): Set Loop Current Error Handling
This command will set the loop current output error handling.
Table 62:
Command-Specific Response Codes for Set Analog Measurement Range Values
Code Class Description
0 Success No Command-Specific Errors
1 - 4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7 Error In Write Protect Mode
8 Warning Set To Nearest Possible Value (Upper or Lower Range Pushed)
9 Error Lower Range Value Too High
10 Error Lower Range Value Too Low
11 Error Upper Range Value Too High
12 Error Upper Range Value Too Low
13 - 15 Undefined
16 Error Access Restricted
17 Undefined
18 Error Invalid Units Code
19 - 31 Undefined
32 Error Busy
33 - 127 Undefined
Table 63: Request Data Bytes for Set Loop Current Error Handling
Byte Format Description
0 Unsigned-8 Analog Output Error Handling:
0: Low;
1: High;
2: Hold;
3: Other value;
1 - 4 Float Error Value, unit is mA