AT600 User’s Manual 107
Chapter 5. Communication
Command 177 (0xB1): Read Pulse Configuration
This command is to read the pulse configuration.
Table 69: Request Data Bytes for Read Pulse Configuration
Byte Format Description
0 Unsigned-8 Channel Number (1/2)
Table 70: Response Data Bytes for Read Pulse Configuration
Byte Format Description
0 Unsigned-8 Channel Number
1 Unsigned-8 Measurement Type:
5: Forward Batch Total;
6: Reverse Batch Total;
7: Net Batch Total;
2 Unsigned-8 Pulse Value Unit
3 - 6 Float Pulse Value
7 - 10 Unsigned-32 Pulse Time, Unit is MS
11 Unsigned-8 Pulse Error Handling:
2: Hold Good Value;
4: Stop;
Table 71:
Command-Specific Response Codes for Read Pulse Configuration
Code Class Description
0 Success No Command-Specific Errors
1Undefined
2 Error Invalid Selection
3-4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7-127 Undefined