Chapter 5. Communication
112 AT600 User’s Manual
Command 186 (0xBA): Write Frequency Configuration
This command is to write the frequency configuration.
Table 84: Request Data Bytes for Write Frequency Configuration
Byte Format Description
0 Unsigned-8 Channel Number(1/2)
1 Unsigned-8 Measurement Type
2 Unsigned-8 Frequency Value Unit
3 - 6 Float Frequency Base Value
7 - 10 Float Frequency Full Value
11 - 14 Unsigned-32 Full Frequency, unit is Hz
15 Unsigned-8 Frequency Error Handling:
0: Low;
1: High;
2: Hold;
3: Value
16 - 19 Unsigned-32 Error Handling value, unit is Hz
Table 85: Response Data Bytes for Write Frequency Configuration
Byte Format Description
0 Unsigned-8 Channel Number(1/2)
1 Unsigned-8 Measurement Type
2 Unsigned-8 Frequency Value Unit
3 - 6 Float Frequency Base Value
7 - 10 Float Frequency Full Value
11 - 14 Float Full Frequency, unit is Hz
15 Unsigned-8 Frequency Error Handling:
0: Low;
1: High;
2: Hold;
3: Value
16 - 19 Unsigned-32 Error Handling value, unit is Hz