REDUCING THE LOAD (TO 200V AND 208V)
If the output voltage is set to 200V and 208V (see “Configuring the CPS” paragraph), the maximum power output of the
CPS is reduced with respect to its rated value, as shown in the graph below:
CONFIGURING THE CPS
Configurations which can be modified by the user from the control panel are listed in the table below.
Selects mimic panel
language language
• English
• Italian
• German
• French
• Spanish
• Polish
• Russian
• Chinese
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
• Normal
• Reduced: does not sound due to the
momentary intervention of the bypass
• On line
• Eco
• Emergency only
Estimated autonomy time
remaining for “battery low”
warning
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.