APS-7000 Series User Manual
114
Simulate Mode Overview
Background
The Simulate function is used to test power
supply fluctuation. This function is able to
simulate common abnormalities in mains
power such as fluctuations in voltage, phase
and frequency. These simulations can be run as
one-off anomalies or cyclic anomalies.
Setting Screen
Overview
Number of repetitions
Test mode
V RANGE
Recall test
Save test
Run test
ON/OFF phase
Trigger output
level
Step Frequency
Step voltage
Step time
Step
Step Overview
The Simulate function is comprised of 6 steps.
Each step is run sequentially in the following
order: Initial, Normal1, Trans1, Abnormal,
Trans2, Normal2, Initial.
Initial
The Initial step is used as the initial
and final settings of the waveform
simulation. This is the standby step
before the test starts and the standby
step after the test ends.
Normal1
This step configures the normal output
conditions that precede the abnormal
conditions.