FusionModule2000 Smart Modular Data Center 
Product Description 
7 Temperature Control System 
 
Copyright © Huawei Technologies Co., Ltd. 
 
app. Obtain the initial startup password during 
deployment. View or obtain the running information 
about the smart cooling product during preventive 
maintenance. (Applicable to V200R001C20 and later 
versions) 
NOTE 
Only Huawei service engineers or authorized service engineers 
are allowed to use the WiFi module. To ensure security, remove 
the WiFi module immediately after use. 
 
Insert the USB flash drive, import and export the 
configuration file, export run logs, and upgrade 
software. 
restart switch for the display 
Dual in-line package (DIP) switch on LCD 
 
7.2.2.2 Function and Features 
Function 
 
Single unit control: Provides logic control for the components of a single smart cooling 
product to ensure that the indoor temperature and humidity meet requirements. 
 
Display operation: Provides a 7-inch touchscreen for you to set parameters for the smart 
cooling product and query its status. 
 
Teamwork control: Enables multiple smart cooling products to work cooperatively, 
distributes thermal loads in an optimal way to dramatically reduce power consumption, 
and provides multiple standby smart cooling products to improve the reliability. 
 
The smart cooling product has the following four remote functions. 
−  Telemetry: supply air temperature, return air temperature, supply air humidity, 
return air humidity, and working status of the smart cooling product. 
−  Teleindication: startup/shutdown states, overvoltage/overcurrent, 
undervoltage/undercurrent, return air overtemperature/undertemperature, return air 
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty. 
−  Telecontrol: smart cooling product startup/shutdown. 
−  Teleadjusting: temperature, humidity, and alarm threshold. 
 
Remote management: You can monitor, manage, and upgrade one or more smart cooling 
products using the remote management function provided by Huawei. 
 
Faults and alarms are recorded and stored. Up to 1500 historical fault and alarm records 
can be stored. 
 
Access logs can be traced back. Historical user login and setting records can be 
displayed. Up to 1000 historical records can be stored. 
Features 
 
The display panel provides a touchscreen with a concise user-friendly interface.