FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Copyright © Huawei Technologies Co., Ltd.
Item
Specifications
humidity at air return vent: 20%; outdoor temperature: 35°C.
Table 7-14 Technical specifications of the indoor unit
Item
NetCol5000-A0
35H4WE0
NetCol5000-A
035H40E0
NetCol5000-
A035H4WE2
NetCol5000-
A035H40E2
Power supply
mode
Single power
supply
Single power
supply
Dual power
supplies
Dual power
supplies
Power system
380415 V, 3PH+N+PE, 50 Hz/60 Hz
Voltage
If upstream voltage fluctuation exceeds the rated voltage±10%, you are
advised to add a voltage regulator. Otherwise, the smart cooling product
may generate alarms frequently and fail to work properly.
Heating
Yes
No
Yes
No
Humidification
Yes
No
Yes
No
Pipe routing
Bottom pipe routing
Top and bottom pipe routing
Condensate
pump
No
Yes
Water pump lift
-
4 m
a: In the preceding table, No indicates that the corresponding model does not provide the
function.
Figure 7-8 Dimensions
Table 7-15 Technical specifications of the outdoor unit
Item
NetCol500-A060
NetCol500-A120
Power supply mode
Power supplied by the
indoor unit
Power supplied by the indoor unit