FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Copyright © Huawei Technologies Co., Ltd.
The water cooling module can be installed in stack mode to maximize the installation
space and reduce the footprint.
The water cooling module uses cooling water for heat exchange to improve the heat
exchange efficiency and improve the energy efficiency of the entire system to 4.0 COP.
Table 7-26 Operating environment specifications with water cooling module
220 V to 240 V AC 1Ph 50 Hz/60 Hz
5%–95% RH (non-condensing)
Inlet water
temperature range of
chilled water
Highest operating
temperature of the
shell pass (°C)
Highest operating
temperature of the
tube pass (°C)
0–4000 m (derated when the altitude is greater than 1000 m)
Enclosed indoor environment in which the temperature and
humidity can be controlled within the ranges of 4°C to 45°C and
5% RH to 90% RH respectively. If the indoor installation position
is ventilated, it should be more than 5 km away from the sea or
pollution sources (such as salt lakes, chemical plants, mineral
plants, thermal power plants, and coal mines).
330 mm x 326 mm x 1417 mm
CE, RoHS, REACH, WEEE, and Chinese industrial product
manufacture license