40°C environment: works for a long term at 125% load.
If the bypass single-phase or three-phase is 150%–200%
overloaded, the bypass can keep working for 5 minutes.
If the bypass single-phase or three-phase is more than
200% overloaded, the bypass can keep working for 1
minute.
If the load exceeds 1000%, the bypass can keep working
for 100 ms.