FusionModule2000 Smart Modular Data Center
Product Description
5 Power Supply and Distribution System
Copyright © Huawei Technologies Co., Ltd.
Class C; nominal discharge
current In (8/20 µs) = 20 kA,
maximum discharge current
Imax (8/20 µs) = 40 kA;
voltage protection level Up
(20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
Three-phase input voltage,
current, frequency, active
power, reactive power, electric
energy, power factor, and
temperature
Supports the Modbus TCP
protocol and Modbus RTU
protocol.
(Optional) Branch temperature monitoring
Table 5-39 Monitoring specifications
Power distribution mains input
Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, circuit breaker status, and surge
protection status
Power distribution branch output
Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status