2105 Model B09 Versatile Storage Server
™ 
 
Dimensions             
Height     1780 mm  70.0 in.    
Width     840 mm  33.0 in.    
Depth     1305 mm  51.0 in.    
Weight     746 kg  1640 lbs.    
Electrical    
Power source loading  3.4 kVA 
Power factor  0.9 
Voltage range (V ac)  200 to 480 
Frequency (hertz)  50 or 60 
Thermal output 
(Maximum) 
11600 Btu/hr 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
(See note)
 
Operating
10 to 38°C
(50 to 90°F)
 
Non-Operating
10 to 43°C
(50 to 110°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  23°C (73°F)  27°C (80°F) 
Noise Emissions¹  Operating 
L
WAd 
7.6 bels 
Clearances  Front  Back  Left  Right 
Service  1145 mm(45 in)  810 mm (32 in)  N/A  N/A 
1.    See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
Note:  The recommended operating temperature is 22°C (72°F) or lower. At lower temperatures, the risk of failure in 
the unit is reduced. If the operating temperature is above 22°C (72°F) for long periods of time, the unit will be 
exposed to a greater risk of failure from external causes.
 
 
 
 