7026 Model B80 
 
Dimensions    
Height  217 mm 8.6 in. 
   5 EIA Units 
Width  482.0 mm 19 in. 
Depth  617 mm 24.3 in. 
Weight    
Minimum configuration  36.5 kg 80.3 lbs. 
Maximum configuration  45.0 kg 99.3 lbs. 
Electrical    
Power source loading (maximum in 
kVA) 
0.46 
Power source loading (typical in kVA)  0.29 
Voltage range (V ac)  100 to 127 or 200 to 240 (autoranging) 
Frequency (hertz)  50 / 60 
Voltage range (V dc)  –48 
Thermal output (maximum)  1536 Btu/hr 
Thermal output (typical)  1024 Btu/hr 
Power requirements (maximum)  450 watts 
Power requirements (typical)  300 watts 
Power factor - US, World Trade, Japan  0.98 
Inrush current²  30 amps 
Maximum altitude³,⁴  2135 m (7000 ft.) 
Temperature Requirements³  Operating⁶
10 to 40°C
(50 to 104°F)
 
Non-Operating
10 to 52°C
(50 to 126°F)
 
Humidity Requirements⁴  Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  27°C (80°F)  27°C (80°F) 
Noise Emissions¹,⁵  Operating  Idle 
L
WAd 
6.1 bels  5.9 bels 
L
pAm 
N/A  N/A 
<L
pA
>
m 
46 dBA  44 dBA 
Clearances  Front  Back  Left  Right 
Install/Air Flow  Maintenance of proper service clearance should allow proper air flow. 
Service  See service clearances for the 7014 T00 Rack 
1.    See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. See noise emissions note 
4. 
2.    Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle. 
3.    The upper limit of the dry bulb temperature must be derated 1 degree C per 137m (450 ft.) above 915m (3000 
ft.). 
4.    The upper limit of the wet bulb temperature must be derated 1 degree C per 274m (900 ft. ) above 305m (1000 
ft.). 
5.    Levels are for a single system installed in a T00 32 EIA rack with the center of the unit approximately 1500 mm 
(59 in.) off the floor. 
6.    For systems with FC 6120: 80/160 GB Internal Tape Drive with VXA Technology or FC 6134: 60/150 GB 16-bit 
8mm Internal Tape Drive, the maximum operating temperature is limited. For additional information about this 
limitation, refer to the following table.
 
 
 
 
72  Site and Hardware Planning Information