7012 POWERstation and POWERserver 34H, 355, 360, 365, 370, and 
375 
 
Dimensions  Desktop  Deskside 
Height  162 mm 6.4 in.  466 mm 18.3 in. 
Width (at pedestal  456 mm 18.0 in.  241 mm 9.5 in. 
for deskside)       
Depth  523 mm 20.6 in.  523 mm 20.6 in. 
Weight       
Minimum  12.7 kg 28 lbs.  12.7 kg 28 lbs. 
Maximum  15.4 kg 34 lbs.  15.4 kg 34 lbs. 
Electrical    
Power source loading  0.29 
(typical in kVA)    
Voltage range (V ac)  100 to 125 or 200 to 240 (autoranging) 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
585 Btu/hr 
Power requirements 
(typical) 
185 watts 
Power factor  0.5 to 0.7 
Inrush current  49 amps at 120 V ac, 98 amps at 240 V ac 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
Operating
16 to 32°C
(60 to 90°F)
 
Non-Operating
10 to 43°C
(50 to 110°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  23°C (73°F)  27°C (80°F) 
Noise Emissions¹  Operating  Idle 
L
WAd 
5.7 bels  5.5 bels 
L
pAm 
45 dBA  45 dBA(desktop) 
   N/A  N/A (deskside) 
<L
pA
>
m 
41 dBA  41 dBA (desktop) 
   38 dBA  38 dBA(deskside) 
Impulsive or 
prominent discrete 
tones
 
No  No 
Clearances  Front  Back  Left  Right 
Install/Air Flow²  152 mm(6 in)  152 mm(6 in)  N/A  N/A 
Service  760 mm(30 in)  N/A  N/A  N/A 
Footprint
2 
Width  Depth 
Desktop  456 mm(18 in)  830 mm(33 in) 
Deskside  241 mm(9.5 in)  828 mm(32.6 in) 
1.    See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
2.    The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
 
 
 
 
18  Site and Hardware Planning Information