7319 Models 100 and 110 Fibre Channel Switches 
 
Dimensions 
Height     86 mm  3.39 in.    
Width     483 mm  19.00 in.    
Depth     495 mm  19.50 in.    
Weight 
Maximum     12.2 kg  27 lbs.    
Electrical 
Power source loading  0.18 
(typical in kVA)    
Voltage range (V ac)  100 to 125 or 200 to 240 (autoranging) 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
570 Btu/hr 
Power requirements 
(typical) 
170 watts 
Power factor  0.98 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
Operating
0 to 40°C
(32 to 104°F)
 
Non-Operating
0 to 50°C
(32 to 125°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  0 to 90%  0 to 90% 
Wet Bulb  27°C (80°F)  27°C (80°F) 
Noise Emissions*  Operating  Idle 
L
WAd 
4.9 bels  4.9 bels 
L
pAm 
N/A  N/A 
Impulsive or 
prominent discrete 
tones
 
No  No 
1.    * See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
 
 
 
316  Site and Hardware Planning Information