3995 Model C62 
 
Dimensions 
Height     991 mm  39.0 in.    
Width     355 mm  14.0 in.    
Width (with 
stabilizers)
 
   464 mm  18.3 in.    
Depth     737 mm  29.0 in.    
Weight 
Minimum (w/o 
cartridges) 
   69 kg  152 lbs    
Maximum (with 52 
cartridges)
 
   85.6 kg  188.4 lbs    
Typical weight of 
cartridge 
   0.32 kg  0.7 lbs    
Electrical 
Power source loading  0.16 
(typical in kVA) @ 
120 V ac 
  
Voltage range (V ac)  100 to 127 or 200 to 240 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
310 Btu/hr 
Power requirements 
(typical) 
90 watts 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
Operating
10 to 38°C
(50 to 100.4°F)
 
Non-Operating
10 to 52°C
(50 to 125.6°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  25.8°C(78.4°F)  27°C(80°F) 
Noise Emissions*  Operating  Idle 
L
WAd 
6 bels  5.5 bels 
L
pAm 
N/A  N/A 
<L
pA
>
m 
N/A  N/A 
Impulsive noise  Yes  Yes 
Prominent discrete 
tones 
No  No 
Clearances  Front  Back  Left  Right 
Install/Air flow  leave open for 
operator panel 
76 mm (3 in)  76 mm (3 in)  76 mm (3 in) 
Service  Install so that it can be moved to an area providing 760 mm (30 in) on each side. 
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
 
 
 