Feature Code  Plug 
Standard Compliance or 
Type 
Countries 
9908 
 
 
AS 3122-1981
250 V, 10 A 
Australia, New Zealand, 
Argentina 
9909 
 
 
NEMA WD-1 6-15P
250 V, 15 A
 
Thailand 
9910 
 
 
NEMA WD-1
5-15P
125 V, 15 A
 
Japan, Others 
9911 
 
 
IEC 320/C14
250 V, 10 A 
All (See note) 
  
Note:   The standard pSeries rack-power cord that provides power from a rack PDU to the system is 
feature code 9911. If customers do not specify a power cord, they will receive feature code 9911. 
Specify feature codes 9900 through 9910 are available on some systems for customers who want to plug 
the system into non-pSeries racks that have PDUs that use regular wall-type outlets. FC 9900 and 9910 
are restricted to a few systems with lower power requirements. Consult the system sales manual for the 
supported power-cord-specify-feature codes. 
-48 Volt DC Rack Power Distribution 
System Racks with -48V DC power distribution (feature codes 6115, 6116, or 6117) have provision for ring 
terminal connection of power to the power distribution panel (PDP) at the top of the rack. The PDP has 
two independent sections for power input and output. Each section of the PDP has a -48 Volt bus bar and 
a -48 Volt Return bus bar. Two holes are provided in each bus bar for input power connection. The input 
power connection holes are sized for 3/8-inch bolts that are approximately 10 mm in diameter. Bolts, ring 
terminals, and wire for -48 volt input power connection are not provided with the rack. 
Properly sized circuit breakers, connectors, and cables to distribute the -48 volts from the PDP to the 
drawers in the rack are provided with the drawers. 
 
 
Chapter 11. Power Cords and Electrical Needs  347