9334 Models 010 and 011 Drawer Expansion Units 
 
Dimensions 
Height     171 mm  6.7 in.    
         (4 EIA units)    
Width     443 mm  17.4 in.    
Depth     686 mm  27.0 in.    
Weight 
Minimum     25 kg  55 lbs.    
Maximum     43 kg  95 lbs.    
Electrical 
Power source loading  0.34 
(typical in kVA)    
Voltage range for 
Model 010 (V ac) 
200 to 240 
Voltage range for 
Model 011 
200 to 240 V ac or -48 V dc 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
580 Btu/hr 
Power requirements 
(typical) 
170 watts 
Power factor  0.5 to 0.7 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
Operating
10 to 40°C
(50 to 104°F)
 
Non-Operating
10 to 52°C
(50 to 125°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  5 to 80% 
Wet Bulb  27°C (80°F)  27°C (80°F) 
Noise Emissions*  Operating  Idle 
L
WAd 
5.5 bels  5.2 bels 
L
pAm 
N/A  N/A 
<L
pA
>
m 
42 dBA  40 dBA 
Impulsive or 
prominent discrete 
tones
 
No  No 
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
 
 
 