7024 Entry Deskside PowerPC Server E Series 
 
Dimensions    
Height  648 mm 25.5 in. 
Width¹  315 mm 12.4 in. 
Depth  450 mm 17.7 in. 
Weight    
Maximum  25 kg 55 lbs. 
Electrical    
Power source loading  0.17 
(typical in kVA)    
Voltage range (V ac)  100 to 127 or 200 to 240 (switchable) 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
375 Btu/hr 
Power requirements 
(typical) 
110 watts 
Power factor  0.5 to 07 
Inrush current⁴  75 amps at 120 V ac, 150 amps at 240 V ac 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements
 
Operating
16 to 32°C
(60 to 90°F)
 
Non-Operating
10 to 43°C
(50 to 110°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  23°C (73°F)  27°C (80°F) 
Noise Emissions²  Operating  Idle 
L
WAd 
5.2 bels  5.0 bels 
L
pAm 
41 dBA  38 dBA 
<L
pA
>
m 
36 dBA  34 dBA 
Impulsive or 
prominent discrete 
tones
 
No  No 
Clearances  Front  Back  Left  Right 
Install/Air Flow³  76mm(3 in)  76mm(3 in)  25mm(1 in)  25mm(1 in) 
Service  466mm(18 in)  N/A  N/A  N/A 
Footprint
3 
Width
365mm(14.4 in) 
Depth
602mm(23.7 in) 
1.    Width measurement includes the optional vertical stand. 
2.    See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
3.    The amount of space needed by the unit during normal operation is indicated by the footprint dimensions. 
4.    Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
 
 
 
 
58  Site and Hardware Planning Information