Magstar
® 
MP 3575 Tape Library Dataserver Model L06 
 
Dimensions 
Height     991 mm  39 in.    
Width     355 mm  14 in.    
Depth     836 mm  37.9 in.    
Weight 
Maximum     71 kg  157 lbs    
Electrical 
Power source loading  0.175 
(typical in kVA)    
Voltage range (V ac)  100 to 127 or 200 to 240 
Frequency (hertz)  50 or 60 
Thermal output 
(typical) 
600 Btu/hr 
Power requirements 
(typical) 
175 watts 
Power factor  0.99 
Maximum altitude  2135 m (7000 ft.) 
Temperature 
Requirements 
Operating
16 to 32°C
(60 to 90°F)
 
Non-Operating
10 to 43°C
(50 to 110°F)
 
Humidity 
Requirements 
Operating  Non-Operating 
(Noncondensing)  8 to 80%  8 to 80% 
Wet Bulb  26°C(79°F)  27°C(80°F) 
Noise Emissions*  Operating  Idle 
L
WAd 
6.6 bels  5.6 bels 
L
pAm 
N/A  N/A 
<L
pA
>
m 
47dBA  34dBA 
Impulsive noise  Yes  Yes 
Prominent discrete 
tones 
No  No 
Clearances  Front  Back  Left  Right 
Install/Air Flow  76 mm (3 in)  76 mm (3 in)  76 mm (3 in)  76 mm (3 in) 
Service  Install so that it can be moved to an area providing 760 mm (30 in) on each side. 
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions. 
 
 
 
Chapter 6. Physical Characteristics of the 3000 Series  251