Technical data
260
IDEC SmartRelay Manual
Fluorescent tubes, uncompen-
sated (25000 switching cycles)
10 x 58 W
(at 230/240 V AC)
10 x 58 W
(at 230/240 V AC)
Short circuit-proof cos 1 Power protection
B16
600A
Power protection
B16
600A
Short-circuit proof cos 0.5 to
0.7
Power protection
B16
900A
Power protection
B16
900A
Derating none; across the en-
tire temperature
range
none; across the en-
tire temperature
range
Parallel output circuits
for power increase
Not permitted Not permitted
Protection of output relay
(if desired)
max. 16 A,
characteristic B16
max. 16 A,
characteristic B16
Switching rate
Mechanical 10 Hz 10 Hz
Ohmic load/lamp load 2 Hz 2 Hz
Inductive load 0.5 Hz 0.5 Hz
FL1C-H12RCC
FL1C-B12RCC
FL1B-M08C2R2