Parameter Groups
‑111‑
Max.: 655.35 Data type: UInt16
Default:
15.86
Change:
At stop
Value Range:
0.01 mH to 655.35 mH
Description
This parameter defines the inductance of the main pole axis (longitudinal axis) of
the synchronous motor.
F1-18
Synchronous motor axis Q inductance
Address:
0xF112
Min.:
0.01
Unit:
mH
Max.: 655.35 Data type: UInt16
Default:
15.86
Change:
At stop
Value Range:
0.01 mH to 655.35 mH
Description
This parameter defines the inductance of the center line (quadrature axis)
between the adjacent pole axes of the synchronous motor rotor.
F1-19
Synchronous motor back EMF coefficient
Address:
0xF113
Min.:
0
Unit:
V
Max.: 6553.5 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0.0 V to 6553.5V
Description
Used to set the RMS value of the motor back EMF at the rated frequency (F1‑04).
F1-20
Filter time constant (PMVVC)
Address:
0xF114
Min.:
0.003
Unit:
‑
Max.: 65.535 Data type: UInt16
Default:
0.1
Change: In real time
Value Range:
0.003 to 65.535
Description
This parameter specifies the filter time constant in PMVVC mode.
F1-21
Oscillation suppression gain (PMVVC)
Address:
0xF115