Parameter Groups
‑177‑
Description
F4‑18 corresponds to the x axis of the AI curve 2 minimum input, that is, the
minimum analog input voltage or current.
F4-19
Percentage corresponding to AI curve 2 minimum input
Address:
0xF413
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
‑100
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
F4‑19 corresponds to the y axis of the AI curve 2 minimum input, that is, the set
value corresponding to the minimum analog input.
F4-20
AI curve 2 maximum input
Address:
0xF414
Min.:
F4‑18
Unit:
V
Max.: 10 Data type: Int16
Default:
10
Change: In real time
Value Range:
F4‑18 to 10.00 V
Description
F4‑20 corresponds to the x axis of the AI curve 2 maximum input, that is, the
maximum analog input voltage or current.
F4-21
Percentage corresponding to AI curve 2 maximum input
Address:
0xF415
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
100
Change: In real time
Value Range:
‑100.0% to 100.0%
Description
F4‑21 corresponds to the y axis of AI curve 2 maximum input, that is, the set value
corresponding to the maximum analog input.
F4-22
AI2 fitter time
Address:
0xF416
Min.:
0
Unit:
s
Max.: 10 Data type: UInt16