Parameter Groups
‑178‑
Default:
0.1
Change: In real time
Value Range:
0.00s to 10.00s
Description
Indicates the software filter time of AI2.
The longer the AI filter time, the stronger the anti‑interference ability and the
slower the response speed to the analog detection. The shorter the AI filter time,
the weaker the anti‑interference ability and the faster the response speed to
analog detection.
When the field analog signal is easy to be interfered, the stability of the analog
signal can be enhanced by increasing the AI filtering time.
F4-23
AI curve 3 minimum input
Address:
0xF417
Min.:
‑10
Unit:
V
Max.: F4‑25 Data type: Int16
Default:
‑10
Change: In real time
Value Range:
‑10.00 V to F4‑25
Description
F4‑23 corresponds to the x axis of the AI curve 3 minimum input, that is, the
minimum analog input voltage or current.
F4-24
Percentage corresponding to AI curve 3 minimum input
Address:
0xF418
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
‑100
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
F4‑24 corresponds to the y axis of AI curve 3 minimum input, that is, the set value
corresponding to the minimum analog input.
F4-25
AI curve 3 maximum input
Address:
0xF419
Min.:
F4‑23
Unit:
V
Max.: 10 Data type: Int16
Default:
10
Change: In real time
Value Range:
F4‑23 to 10.00 V