Parameter Groups
‑179‑
Description
F4‑25 corresponds to the x axis of AI curve 3 maximum input, that is, the
maximum analog input voltage or current.
F4-26
Percentage corresponding to AI curve 3 maximum input
Address:
0xF41A
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
100
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
F4‑26 corresponds to the y axis of AI curve 3 maximum input, that is, the set value
corresponding to the maximum analog input.
F4-27
AI3 filter time
Address:
0xF41B
Min.:
0
Unit:
s
Max.: 10 Data type: UInt16
Default:
0.1
Change: In real time
Value Range:
0.00s to 10.00s
Description
Indicates the software filter time of AI3.
The longer the AI filter time, the stronger the anti‑interference ability and the
slower the response speed to the analog detection. The shorter the AI filter time,
the weaker the anti‑interference ability and the faster the response speed to
analog detection.
When the field analog signal is easy to be interfered, the stability of the analog
signal can be enhanced by increasing the AI filtering time.
F4-28
Pulse minimum input
Address:
0xF41C
Min.:
0
Unit:
kHz
Max.: F4‑30 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 kHz to F4‑30
Description