Parameter Groups
‑180‑
When the DI5 high‑speed pulse is used to set the main frequency, the relationship
curve between the pulse frequency and the frequency reference must be defined.
The frequency reference is the percentage corresponding to the maximum
frequency (F0‑10). The x axis of the curve represents the DI5 pulse frequency and
the y axis represents the percentage corresponding to the maximum frequency
(F0‑10). The curve is a two‑point curve, which includes the minimum pulse input
and maximum pulse input points.
F4‑28 corresponds to the x axis of the minimum pulse input, that is, the minimum
input frequency of the pulse.
F4-29
Percentage corresponding to pulse minimum input
Address:
0xF41D
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
0
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
F4‑29 corresponds to the y axis of the minimum pulse input, that is, the set value
corresponding to the minimum pulse input.
F4-30
Pulse maximum input
Address:
0xF41E
Min.:
F4‑28
Unit:
kHz
Max.: 100 Data type: UInt16
Default:
50
Change: In real time
Value Range:
F4‑28 to 100.00 kHz
Description
F4‑30 corresponds to the x axis of the maximum pulse input, that is, the maximum
input frequency of the pulse.
F4-31
Percentage corresponding to pulse maximum input
Address:
0xF41F
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
100
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
F4‑31 corresponds to the y axis of the maximum pulse input, that is, the set value
corresponding to the maximum pulse input.